This series of instruments has been designed for the management of static units (that is, without evaporator fans) operating in low temperature conditions (below  0°C), that therefore require defrosting by electric heater or the injection of hot gas. As well as the thermometer and thermostat functions, these instruments also manage the defrost actuator. The frequency and the duration of the defrost can be set by parameter. Once having reached the set temperature (connecting a probe to the evaporator) or the set time has elapsed (also used as a safety feature for the first mode), the defrost is automatically terminated.
 

Technical features 

Power supply

IR33Y00*: 12 Vac (-15% to +10% ) or 12 Vdc (0% to +50%), 50/60 Hz,
IR33Y0L*
: 12/24 Vac (-15% to +10% ), 50/60 Hz;
IR33Y0E*: 230 Vac (-15% to +10% ), 50/60 Hz;
IR33Y0H*: 115/230 Vac (-15% to +10% ), 50/60 Hz

Operating conditions

-10 to 65°C, <90% rH non-condensing

Storage conditions

-20 to70°C, <90% rH non-condensing

Regulation range

-50 to 90°C with standard CAREL NTC probes
-40 to 150°C wide range NTC probes;
-50 to 150°C with PTC probes

Inputs

IR33Y00*/L*/H*: 2 for NTC or PTC probes, 2 digital inputs;
IR33Y0E*: 2 for NTC or PTC probes, 1 digital inputs

Outputs

IR33Y00*/L*: 1 relay 250 Vac, 12 (2) A res. and 1 relay 250 Vac, 8 (4) A res. or 1 relay 250 Vac, 12 (2) A res. and 2 relay 250 Vac, 8 (4) A res.;
IR33Y0E*: 2 relay 250 Vac, 8 (4) A res. or 2 relay 250 Vac, 8 (4) A res. and 1 relay 250 Vac, 5 (1) A res. or 1 relay 250 Vac, 12 (2) A res and 1 relay 250 Vac, 5 (1) A res.;
IR33Y0H*: 1 relay 250 Vac, 12 (2) A and 1 relay 250 Vac, 8 (4) A res. oppure 1 relay 250 Vac, 12 (2) A and 2 relay 250 Vac, 8 (4) A res.

Index of protection

IP65 with panel mounting and gasket fitted

Installation

panel mounting

 

 